4 FAQs about Spatial distance between battery cabinets

How much space do you need for a battery system?

Spaces about battery systems shall comply with 110.26. Working space shall be measured from the edge of the battery cabinet, racks, or trays. For battery racks, there shall be a minimum clearance of 25 mm (1 in.) between a cell container and any wall or structure on the side not requiring access for maintenance.

What is the minimum clearance for a battery rack?

For battery racks, there shall be a minimum clearance of 25 mm (1 in.) between a cell container and any wall or structure on the side not requiring access for maintenance. Battery stands shall be permitted to contact adjacent walls or structures, provided that the battery shelf has a free air space for not less than 90 percent of its length.

Where should a battery cabinet be installed?

The battery cabinet must be installed adjacent to the power cabinet. The following diagram shows the equipment layout for a typical new indoor Macrocell site. Notes: The cabinets may be placed with zero clearance to the rear wall. The cabinets may be placed with zero clearance to the side wall, however some clearance is recommended.

What is the minimum space between ezbfi frame and UMTS macrocell cabinet?

Minimum space between the EZBFi frame and the adjacent cabinet or frame is 57 mm (2.24 in.) (if the edge of the template is cut at the dotted line). The following diagram shows the clearance requirements for the indoor UMTS Macrocell cabinet from the top of the cabinet to the cable rack and from the top of the cable rack to the ceiling.

View/Download Spatial distance between battery cabinets [PDF]

PDF version includes complete article with source references. Suitable for printing and offline reading.